If you need know more about perforated cable tray. Welcome to visit our factory or send us enquiry.
41x21x2.5mm Load Rating & Deflection
Max load notes: loading is static and should be applied as a Uniformly Distributed Load. Published values are for plain channels, based on a simply supported beam.
Span (mm) | Max. Allowable Load (kg) |
250 | 333 |
500 | 166 |
750 | 111 |
1500 | 55 |
3000 | 28 |
Slotting Details
28.5 x 14mm slots are punched continuously at 50mm centres 41x62x2.5mm Load Rating & Deflection
Max load notes: loading is static and should be applied as a Uniformly Distributed Load. Published values are for plain channels, based on a simply supported beam.
Span (mm) | Max. Allowable Load (kg) |
250 | 1902 |
500 | 951 |
750 | 634 |
1500 | 317 |
3000 | 159 |
Slotting Details
28.5 x 14mm slots are punched continuously at 50mm centres 41x21x1.6mm Load Rating & Deflection
Max load notes: loading is static and should be applied as a Uniformly Distributed Load. Published values are for plain channels, based on a simply supported beam.
Span (mm) | Max. Allowable Load (kg) |
250 | 262 |
500 | 131 |
750 | 87 |
1500 | 44 |
3000 | 22 |
Slotting Details
28.5 x 14mm slots are punched continuously at 50mm centres 41x41x1.6mm Load Rating & Deflection
Max load notes: loading is static and should be applied as a Uniformly Distributed Load. Published values are for plain channels, based on a simply supported beam.
Span (mm) | Max. Allowable Load (kg) |
250 | 728 |
500 | 364 |
750 | 243 |
1500 | 121 |
3000 | 61 |
Slotting Details
28.5 x 14mm slots are punched continuously at 50mm centres 41x41x2.5mm Load Rating & Deflection
Max load notes: loading is static and should be applied as a Uniformly Distributed Load. Published values are for plain channels, based on a simply supported beam.
Span (mm) | Max. Allowable Load (kg) |
250 | 980 |
500 | 490 |
750 | 327 |
1500 | 163 |
3000 | 82 |
Slotting Details
28.5 x 14mm slots are punched continuously at 50mm centres